2012-07-12 10:19:48 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| 1. THE STRUCTURAL PLAN SUBMITTED IS EXTREMELY |
| CONFUSING. A PLAN PREPARED BY GUS TARNOWSKI, PE WAS |
| SIGNED AND SEALED BY RIZA ALTAN, PE WITH THE LANGUAGE |
| "FOR REFERENCE ONLY." WHO IS TAKING RESPONSIBILITY FOR |
| THE DESIGN OF THIS STRUCTURE? IF RIZA ALTAN IS TAKING |
| OVER THE WORK OF TARNOWSKI, HAS MR. TARNOWSKI BEEN |
| ADVISED AS REQUIRED BY FAC 61G15-27.001? IN THE CASE OF |
| A SUCCESSOR ENGINEER REUSING ANOTHER ENGINEER'S PLAN, |
| THE OTHER ENGINEER'S TITLE BLOCK SHOULD BE REMOVED AND |
| THE SUCCESSOR ENGINEER'S TITLE BLOCK INCLUDED. OR, IS |
| MR. RIZA AN EMPLOYEE OF TARNOWSKI ENGINEERING, AND |
| AUTHORIZED TO USE THAT TITLE BLOCK? THE TITLE BLOCK |
| SHOULD ALSO INCLUDE THE PRINTED NAME AND LICENSE NUMBER |
| OF THE INDIVIDUAL SEALING THE PLAN. THE SEAL SHOULD |
| INCLUDE A DATE. |
| |
| A STRUCTURAL PLAN TO SHOW HOW THIS IMPROVEMENT COMPLIES |
| WITH FBC RESIDENTIAL 301.1, WIND LOADS, IS REQUIRED. |
| |
| 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| ROOF PANELS, FAC9N-3. |
| |
| 3. SEE FBC RESIDENTIAL TABLE 302.1 FOR SEPARATION |
| REQUIREMENTS. PROVIDE FIRE RESISTANCE INFORMATION AS |
| REQUIRED BY THE TABLE. |
| |
| 4. VALUE IS TO INCLUDE LABOR AND MATERIALS, FBC 108.3. |
| |
| |