2012-06-29 15:50:09 | RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- ENGINEER (CARL A. WILSON) TO SIGN AND SEAL DRAWINGS |
| AS REQUIRED BY FLORIDA STATUTE 471 WHEN SUBMITTING |
| DOCUMENTS FOR PUBLIC RECORDS. |
| |
| 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 101.4.3 AND 103.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| 3- ENGINEER TO PROVIDE ALL THE DESIGN PARAMETERS |
| INFORMATION ON THE PLANS. SPECIFY CURRENT CODE IN |
| EFFECT, SPECIFY THE BUILDING EXPOSURE, SPECIFY THE |
| ULTIMATE AND NOMINAL WIND LOADS. AND SPECIFY THE DESIGN |
| PRESSURES FOR DOORS AND WINDOWS INCLUDING THE GARAGE |
| DOOR. SEC. R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL |
| CODE. |
| |
| NOTE: ACCORDING TO SEC. R301.2.1.4.3, THIS BUILDING IS |
| LOCATED ON EXPOSURE "C", |
| |
| 4- COLUMN ELEVATION DETAIL: ENGINEER TO CLARIFY HOW IS |
| THE STEEL COLUMN GOING TO BE FASTENED AT THE BASE. |
| PROVIDE COMPLETE SPECIFICATIONS FOR COLUMN BASE AND |
| CLARIFY WHY ONLY ONE 3/8" DIA. ANCHOR WAS SPECIFIED. |
| HOW MUCH ANCHOR EMBEDMENT IS REQUIRED INTO THE CONCRETE |
| FOOTING?. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. |
| |
| 5- PROVIDE MANUFACTURER SPECIFICATIONS FOR DOORS AND |
| WINDOWS SHOWING COMPLIANCE WITH THE ENERGY EFFICIENCY |
| REQUIRED BY THE ENERGY CALCULATIONS AND TABLE 402.1.1 |
| OF THE 2010 FBC-ENERGY CONSERVATION. |
| |
| 6- PROVIDE PRODUCT APPROVAL (2 COPIES). SEC. 107.2 CITY |
| AMENDMENTS TO FBC: |
| A) GARAGE DOOR. NOA 09-0604.03 SUBMITTED WAS SUPERSEDED |
| BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE AND |
| DOWNLOAD CURRENT NOA. |
| |
| B) SINGLE HUNG WINDOWS. NOA 11-0705.09 SUBMITTED WAS |
| SUPERSEDED BY MIAMI-DADE. DOWNLOAD CURRENT NOA. |
| |
| 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| |
| 8- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR STORM |
| SHUTTERS INSTALLATION. CLEARLY IDENTIFY SPECIFIC |
| MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE |
| USED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| |