Plan Review Notes For Permit 12060141
Permit Number 12060141
Review Stop P
Sequence Number 1
Notes
Date Text
2012-06-19 09:26:492010 FBC
  
 DENIED BY PLUMBING
  
 1) ACCORDING TO THE MANUFACTURER'S PUMP CURVE FOR THE
 INTELLIFLO VS 3050, THE MAXIMUM FLOW RATE IS 145 GPM AT
 50 TDH. A 3" SUCTION LINE IS REQUIRED TO ACHIEVE THE 8
 FEET PER SECOND MAXIMUM VELOCITY ALLOWED FOR SUCTION
 PIPING BY FBC R4101.6.3. ANSI/APSP 7-06 SECTION 4.4
 REQUIRES THE MAXIMUM SYSTEM FLOW RATE FOR CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW