Plan Review Notes
Plan Review Notes For Permit 12060082
Permit Number 12060082
Review Stop B
Sequence Number 1
Notes
Date Text
2012-06-20 14:50:402010 FBC
  
 DENIED BY BUILDING
  
 1) THE SCOPE OF WORK THAT IS SPECIFIED ON SHEET A-1,
 INDICATES THAT SEVERAL WINDOWS IN THE DETACHED GARAGE
 SUITE ARE TO BE REPLACED. SPECIFY THE LOCATION AND
 SIZES OF THE WINDOWS THAT ARE BEING REPLACED ON THE
 PLANS. CITY AMENDMENTS 107.2.1, FBC EXISTING BUILDING
 604.1 AND 606.4
  
 2) SPECIFY THE REQUIRED WINDOW WIND LOAD DESIGN
 PRESSURES FOR THE WINDOWS THAT ARE BEING REPLACED. FBC
 EXISTING BUILDING 606.4
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW
 WINDOWS THAT MEET THE REQUIRED COMPONENT & CLADDING
 PRESSURES AS REQUIRED BY DCA RULE 9N-3.
  
 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 5) FBC EXISTING BUILDING 606.4 REQUIRES OPENING
 PROTECTION FOR THE WINDOWS IF THE AGGREGATE AREA OF THE
 GLAZING IN THE REPLACED COMPONENTS EXCEEDS 25 PERCENT
 OF THE AGGREGATE AREA OF THE GLAZED OPENINGS IN THE
 DWELLING OR DWELLING UNIT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]