Plan Review Notes For Permit 12060082 |
Permit Number |
12060082 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-06-20 14:50:40 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE SCOPE OF WORK THAT IS SPECIFIED ON SHEET A-1, | | INDICATES THAT SEVERAL WINDOWS IN THE DETACHED GARAGE | | SUITE ARE TO BE REPLACED. SPECIFY THE LOCATION AND | | SIZES OF THE WINDOWS THAT ARE BEING REPLACED ON THE | | PLANS. CITY AMENDMENTS 107.2.1, FBC EXISTING BUILDING | | 604.1 AND 606.4 | | | | 2) SPECIFY THE REQUIRED WINDOW WIND LOAD DESIGN | | PRESSURES FOR THE WINDOWS THAT ARE BEING REPLACED. FBC | | EXISTING BUILDING 606.4 | | | | 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW | | WINDOWS THAT MEET THE REQUIRED COMPONENT & CLADDING | | PRESSURES AS REQUIRED BY DCA RULE 9N-3. | | | | 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | AMENDMENTS 107.3.4.1 | | | | 5) FBC EXISTING BUILDING 606.4 REQUIRES OPENING | | PROTECTION FOR THE WINDOWS IF THE AGGREGATE AREA OF THE | | GLAZING IN THE REPLACED COMPONENTS EXCEEDS 25 PERCENT | | OF THE AGGREGATE AREA OF THE GLAZED OPENINGS IN THE | | DWELLING OR DWELLING UNIT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|