Plan Review Notes For Permit 12060062 |
Permit Number |
12060062 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2012-08-03 19:29:20 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | COMMENTS FROM PREVIOUS LIST: | | | | 1. OK. | | | | 2. THE LIFE SAFETY PLAN DOES NOT SHOW WHICH OPENINGS | | YOU PROPOSE TO COVER. PLEASE CORRELATE WITH | | INSTALLATION SCHEDULE OR YOUR PREVIOUSLY SUBMITTED | | FLOOR PLAN. IT IS NOT CLEAR WHICH DOORS ARE TO BE | | BLOCKED, FBC 1003.6. | | | | REVISED PLAN SHOWS REQUIRED EXIT DOORS IN ASSEMBLY | | OCCUPANCY PROPOSED TO BE COVERED BY HURRICANE SHUTTERS. | | THERE IS NO PROVISION ALLOWING THIS USE OF SHUTTERS. | | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. | | | | IF YOU WISH TO PROVIDE RATIONALE FOR BLOCKING REQUIRED | | EXITS IN AN ASSEMBLY OCCUPANCY, PLEASE SUBMIT A LETTER | | ADDRESSED TO ROBERT BROWN, ABO (VIA EMAIL), AND IT WILL | | BE FORWARDED TO HIM. | | | | | | | | |
|