Plan Review Notes
Plan Review Notes For Permit 12060062
Permit Number 12060062
Review Stop B
Sequence Number 3
Notes
Date Text
2012-08-03 19:29:20****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. OK.
  
 2. THE LIFE SAFETY PLAN DOES NOT SHOW WHICH OPENINGS
 YOU PROPOSE TO COVER. PLEASE CORRELATE WITH
 INSTALLATION SCHEDULE OR YOUR PREVIOUSLY SUBMITTED
 FLOOR PLAN. IT IS NOT CLEAR WHICH DOORS ARE TO BE
 BLOCKED, FBC 1003.6.
  
 REVISED PLAN SHOWS REQUIRED EXIT DOORS IN ASSEMBLY
 OCCUPANCY PROPOSED TO BE COVERED BY HURRICANE SHUTTERS.
 THERE IS NO PROVISION ALLOWING THIS USE OF SHUTTERS.
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  
 IF YOU WISH TO PROVIDE RATIONALE FOR BLOCKING REQUIRED
 EXITS IN AN ASSEMBLY OCCUPANCY, PLEASE SUBMIT A LETTER
 ADDRESSED TO ROBERT BROWN, ABO (VIA EMAIL), AND IT WILL
 BE FORWARDED TO HIM.
  
  
  
  