Plan Review Notes For Permit 12050811 |
Permit Number |
12050811 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-05-29 16:42:11 | RE-ROOF BUILDING REVIEW COMMENTS. | | 2010 FBC. | | | | 1- ENGINEER TO PROVIDE THE RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #7. FLAT ROOF BASE SHEET | | FASTENING INFORMATION SUBMITTED BY THE ENGINEER IS THE | | SAME AS SPECIFIED ON THE NOA 11-0425.07 SUBMITTED. THIS | | NAILING IS GOOD ONLY FOR ROOF ZONE #1. THAT'S WHY RAS | | 117 CALCULATIONS FOR PERIMETER AND CORNER AREAS ARE | | REQUIRED TO PROVIDE THE ENHANCED NAIL FASTENING TO MEET | | THE DESIGN PRESSURES REQUIRED BY SEC. 1609 OF FBC. | | | | 2- ENGINEER TO REVISE THE DESIGN PRESSURES. ACCORDING | | TO SEC. 1609.4.3 THIS BUILDING IS LOCATED ON EXPOSURE | | "C" NOT "B". REVISE AS REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|