Plan Review Notes For Permit 12050683 |
Permit Number |
12050683 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-05-23 12:30:15 | RE-ROOF BUILDING REVIEW COMMENTS. | | 2010 FBC. | | | | 1- ACCORDING TO SEC. 1609.4.3 THIS BUILDING IS LOCATED | | ON EXPOSURE "D" NOT EXPOSURE "C". NEED TO REVISE THE | | DESIGN PRESSURES CALCULATIONS AND THE RECOMMENDED BASE | | SHEET ATTACHMENT PATTERN TO MEET THE NEW CALCULATED | | DESIGN PRESSURES. | | | | 2- FLAT ROOF NOA 09-0820.11 SUBMITTED WAS SUPERSEDED BY | | MIAMI-DADE. NEED TO VISIT THE MIAMI-DADE WEBSITE AND | | DOWNLOAD CURRENT NOA. PROVIDE 2 COPIES. DCA RULE 9N-3. | | NOTE: SUBMIT THE NOA ALONE. FLORIDA PRODUCT APPROVAL | | FL735-R4 WILL NEED TO BE REVISED BY THE FLORIDA | | BUILDING COMMISSION ACCORDINGLY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|