2012-05-21 16:57:26RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE.
  
 1- SELECTED FLAT ROOF ASSEMBLY W-32 ON PAGE 9 OF 30
 CAN'T BE USED IN THIS HOUSE. THE MAXIMUM DESIGN
 PRESSURES FOR THIS ASSEMBLY IS -90PSF. THIS ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.2.1.4.3. DESIGN PRESSURES ON BONDED ASSEMBLIES ARE
 THE MAXIMUM DESIGN PRESSURES AND NO RATIONAL ANALYSIS
 IS ALLOWED. SEE NOTE #9 ON PAGE 2 OF 30.
  
 2- NEED TO SELECT ASSEMBLY WITH HIGHER DESIGN PRESSURES
 TO MEET THE DESIGN PRESSURES OF THE PERIMETER AND
 CORNER AREAS OR ANY OTHER ASSEMBLY THAT ALLOWS NAIL
 ENHANCING THRU ENGINEERING CALCULATIONS. ACCORDING TO
 SEC. R301.2.1.4.3 THIS HOUSE IS LOCATED ON EXPOSURE
 "D". DESIGN PRESSURES FOR EXPOSURE "D" ARE A LOT HIGHER
 THAN THE -90PSF THAT THE SELECTED ASSEMBLY CAN RESIST.
  
 3- ASSEMBLIES WITH MECHANICALLY FASTENED BASE SHEET ARE
 THE ONES THAT ALLOW NAIL ENHANCING. SUCH CALCULATIONS
 ARE DONE USING THE RAS 117 CALCULATIONS. THIS
 CALCULATIONS NEED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL AS REQUIRED BY NOTE #8 ON PAGE 2 OF 30 OF
 SUBMITTED PRODUCT APPROVAL. DESIGN PROFESSIONAL DOING
 THE CALCULATIONS NEED TO CONSIDER THE EXPOSURE "D" OF
 THIS BUILDING. SEC. R301.2.1.4.3.
  