2012-06-01 16:00:24 | BUILDING PLAN REVIEW |
| PERMIT: 12050553 |
| ADD: 2271 PALM BEACH LAKES / SUITE "C" |
| CONT: RAPP CONSTRUCTION |
| TEL: (561)842-3299 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SHEET A3.1 FLOOR PLAN/ LIFE SAFETY PLAN, PLEASE |
| INDICATE WHERE THE ACCESS AISLES ARE LOCATED AND WHERE |
| THE DISPLAYS, FURNISHINGS AND OR KIOSK ARE LOCATED. |
| PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1017.1 & |
| 1017.3. |
| |
| 2) PLANS DO NOT INDICATE THE SQUARE FOOTAGE OF THE |
| STORAGE AREA AT THE BACK OF THE STORE, AND THE TOTAL |
| SQUARE FOOTAGE OF THE STORE. IF THE STORAGE AREA IS |
| OVER 10% OF THE TOTAL FLOOR AREA THEN IT IS CONSIDERED |
| A ACCESORY OCCUPANCY WHICH WILL MKE THIS A MIXED |
| OCCUPANCY. PLEASE REVIEW SECTIONS 2010 FBC-B 508.2.1 |
| AREA LIMITATIONS, |
| 508.3 NON-SEPERATED OCCUPANCIES AND 508.4 508.4 |
| SEPERATED OCCUPANCIES. PLEASE ALSO REVIEW SECTION |
| SECTION 311.2 IT APPEARS THAT FURNITURE IS CONSIDERED A |
| S1 OCCUPANCY. TABLE 508.4. INDICATES NO OCCUPANCY |
| SEPERATION IS REQUIRED BETWEEN MERCANTILE AND A S1 |
| STORAGE OCCUPANCY. |
| |
| 3) SHEET 3.1 INDICATES SPRAY INSULATION R20 TO THE |
| UNDER SIDE OF THE ROOF DECK, PLEASE PROVIDE |
| MANUFACTURES SPECS ON THE TYPE OF INSULATION TO BE |
| INSTALLED? |
| IF A FOAM PLASTIC INSULATION IS TO BE INSTALLED PLEASE |
| PROVIDE COMPLIANCE WITH SMOKE DEVELOPMENT & FLAME |
| SPREAD, AS WELL AS COMPLIANCE WITH 2603.4.1.6 IGNITION |
| BARRIER. |
| |
| 4) SHEET 1.1 CODE SUMMARY INDICATES A SINGLE DRINKING |
| FOUNTAIN PLEASE REVIEW THE 2010 FBC-ACCESSIBILITY CODE |
| SCOPING 211.2 MINIMUM NUMBER. NO FEWER THAN TWO |
| DRINKING FOUNTAINS SHALL BE PROVIDED.ONE DRINKING |
| FOUNTAIN SHALL COMPLY WITH 602.1THROUGH 602.6 AND ONE |
| DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. |
| |