2012-06-01 16:00:24BUILDING PLAN REVIEW
 PERMIT: 12050553
 ADD: 2271 PALM BEACH LAKES / SUITE "C"
 CONT: RAPP CONSTRUCTION
 TEL: (561)842-3299
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A3.1 FLOOR PLAN/ LIFE SAFETY PLAN, PLEASE
 INDICATE WHERE THE ACCESS AISLES ARE LOCATED AND WHERE
 THE DISPLAYS, FURNISHINGS AND OR KIOSK ARE LOCATED.
 PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1017.1 &
 1017.3.
  
 2) PLANS DO NOT INDICATE THE SQUARE FOOTAGE OF THE
 STORAGE AREA AT THE BACK OF THE STORE, AND THE TOTAL
 SQUARE FOOTAGE OF THE STORE. IF THE STORAGE AREA IS
 OVER 10% OF THE TOTAL FLOOR AREA THEN IT IS CONSIDERED
 A ACCESORY OCCUPANCY WHICH WILL MKE THIS A MIXED
 OCCUPANCY. PLEASE REVIEW SECTIONS 2010 FBC-B 508.2.1
 AREA LIMITATIONS,
 508.3 NON-SEPERATED OCCUPANCIES AND 508.4 508.4
 SEPERATED OCCUPANCIES. PLEASE ALSO REVIEW SECTION
 SECTION 311.2 IT APPEARS THAT FURNITURE IS CONSIDERED A
 S1 OCCUPANCY. TABLE 508.4. INDICATES NO OCCUPANCY
 SEPERATION IS REQUIRED BETWEEN MERCANTILE AND A S1
 STORAGE OCCUPANCY.
  
 3) SHEET 3.1 INDICATES SPRAY INSULATION R20 TO THE
 UNDER SIDE OF THE ROOF DECK, PLEASE PROVIDE
 MANUFACTURES SPECS ON THE TYPE OF INSULATION TO BE
 INSTALLED?
 IF A FOAM PLASTIC INSULATION IS TO BE INSTALLED PLEASE
 PROVIDE COMPLIANCE WITH SMOKE DEVELOPMENT & FLAME
 SPREAD, AS WELL AS COMPLIANCE WITH 2603.4.1.6 IGNITION
 BARRIER.
  
 4) SHEET 1.1 CODE SUMMARY INDICATES A SINGLE DRINKING
 FOUNTAIN PLEASE REVIEW THE 2010 FBC-ACCESSIBILITY CODE
 SCOPING 211.2 MINIMUM NUMBER. NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED.ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.1THROUGH 602.6 AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715