Plan Review Notes For Permit 12050552
Permit Number 12050552
Review Stop M
Sequence Number 1
Notes
Date Text
2012-05-29 10:36:47PLANS DENIED
  
 1. APPLICATION STATES THAT A/C SYSTEM IS TO BE
 REPLACED. PROVIDE MORE INFORMATION REGARDING SCOPE OF
 WORK, FBC 2010 107.3.5.3.
  
 IF THIS IS AN EXACT CHANGEOUT, TWO SETS OF THE A/C
 CHANGE OUT COMPLIANCE FORM REQUIRED:
  
 HTTP://WWW.WPB.ORG/CONSTRUCTION/PDF/AC%20CHANGEOUT.PDF
  
 IF THIS IS A NEW INSTALLATION, PROVIDE A PLAN FOR
 PROPOSED WORK. PLEASE NOTE THAT I WAS UNABLE TO LOCATE
 AN EXISTING MECHANICAL SYSTEM IN OUR RECORDS FOR THIS
 PROPERTY. OUR RECORDS SHOW A WALL UNIT INSTALLATION IN
 1971, BUT I WAS UNABLE TO LOCATE A PERMIT FOR CENTRAL
 A/C.
  
 2. PROVIDE A REASONABLE VALUE / COST BREAKDOWN FOR
 PROPOSED WORK, FBC 2010 109.3.
  
 3. FBC 2010 ENERGY, PROVIDE DOCUMENTS REQUIRED BY
 SECTION 101.4.7.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR