2012-05-18 15:23:01 | RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW COMMENTS. |
| 2010 FLORIDA RESIDENTIAL CODE. |
| |
| 1- ACCORDING TO SEC. R301.2.1.4.3 THIS HOUSE IS LOCATED |
| ON EXPOSURE "D" NOT "C". REVISE CALCULATIONS AS |
| REQUIRED. AND, REVISE INSTALLATION SCHEDULE AS |
| REQUIRED. |
| |
| 2- DESIGN PRESSURES SHOWN ON SUBMITTED CALCULATIONS ARE |
| TOO LOW EVEN FOR EXPOSURE "C". ENGINEER RESPONSIBLE FOR |
| THE CALCULATIONS TO PROVIDE ACTUAL CALCULATIONS AS |
| REQUIRED BY SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. AND, |
| PROVIDE CALCULATIONS WITH ORIGINAL SEAL AND SIGNATURE |
| AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. AND, |
| PROVIDE 2 COPIES. |
| ***NOTE: COORDINATE CALCULATIONS WITH ITEM #1 ABOVE. |
| |
| 3- ANCHOR SCHEDULE USED IS FOR CONCRETE APPLICATIONS. |
| SEE SHEET 9 OF DRAWINGS SUBMITTED. PROVIDE PROOF THAT |
| EXISTING HOUSE HAS CONCRETE LINTELS AND CONCRETE SILLS |
| WITH THE MINIMUM CONCRETE STRENGTH (3192 PSI MIN.) AS |
| INDICATED ON THE ANCHOR SCHEDULE. OTHERWISE USE THE |
| ANCHOR SCHEDULE FOR HOLLOW CONCRETE BLOCK AS SHOWN ON |
| SHEET #10. REVISE ANCHOR SPACING ON THE SHUTTERS |
| INSTALLATION SCHEDULE AS REQUIRED. SEC. 107.2.1.3 CITY |
| AMENDMENTS. |
| |
| 4- SHUTTER SPAN SPECIFIED ON THE SHUTTERS INSTALLATION |
| SCHEDULE IS THE SAME AS THE OPENING HEIGHT. ACCORDING |
| TO THESE NUMBERS THE MINIMUM EDGE DISTANCE OF 2.5" IS |
| NOT POSSIBLE. ALSO, NEED TO CONSIDER THAT THE EDGE |
| DISTANCE EXCLUDES THE STUCCO THICKNESS. REVISE AS |
| REQUIRED. SEC. 107.2.1.3. |
| |