Plan Review Notes
Plan Review Notes For Permit 12050436
Permit Number 12050436
Review Stop M
Sequence Number 1
Notes
Date Text
2012-05-17 14:15:18ON THE 1ST PAGE OF THE PLANS IT SHOWS 15 NEW PIPE AND
 SPRINKLERS
 AND 16 RELOCATED PIPE AND SPRINKLERS . PAGE 3 OF PLANS
 SHOW A LOT MORE.
 PLEASE CLARIFY.
 REFER TO SECTION 633.021 (S) (E) FLORIDA STATUTES 49
 HEADS OR MORE PLANS
 MUST BE ENGINEERED.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]