2012-05-16 09:41:17 | FIRE DEPARTMENT REVIEW ***DENIED**** |
| |
| ADDRESS: 315 SOUTH FLAGLER DRIVE |
| PERMIT # 12050436 |
| CONTRACTOR: FRED MCGILVRAY INC. |
| PHONE: 561 471-3349 |
| |
| |
| 1. THE SCOPE OF WORK SHALL BE INDICATED ON PLANS. |
| 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE |
| FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA |
| EDITION OF NFPA 1 AND NFPA 101. |
| 3. ALL DEMOLITION WORK SHALL CONFORM TO THE |
| REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| SHALL BE REMOVED FROM THE SITE DAILY. |
| 4. FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| 5. FOR SYSTEM PRESSURES EXCEEDING 100 PSI, PENDENT |
| SPRINKLERS SHALL BE PROTECTED FROM UPWARD MOVEMENT. |
| HANGERS SHALL BE LOCATED WITHIN 12-INCHES OF THE DROP |
| ELBOW. INDICATE THE HANGER TYPE OR METHOD TO BE USED |
| FOR RESTRAINING UPWARD MOVEMENT. |
| 6. FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES |
| SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE |
| DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE |
| SPRINKLERS. |
| |
| |
| |
| DERRICK L. DANIELS, BATTALION CHIEF |
| WEST PALM BEACH FIRE RESCUE |
| OFFICE OF THE FIRE MARSHAL |
| (561) 805-6722 |
| |