2012-05-16 09:41:17FIRE DEPARTMENT REVIEW ***DENIED****
  
 ADDRESS: 315 SOUTH FLAGLER DRIVE
 PERMIT # 12050436
 CONTRACTOR: FRED MCGILVRAY INC.
 PHONE: 561 471-3349
  
  
 1. THE SCOPE OF WORK SHALL BE INDICATED ON PLANS.
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 3. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 4. FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
 5. FOR SYSTEM PRESSURES EXCEEDING 100 PSI, PENDENT
 SPRINKLERS SHALL BE PROTECTED FROM UPWARD MOVEMENT.
 HANGERS SHALL BE LOCATED WITHIN 12-INCHES OF THE DROP
 ELBOW. INDICATE THE HANGER TYPE OR METHOD TO BE USED
 FOR RESTRAINING UPWARD MOVEMENT.
 6. FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS.
  
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6722
  