Plan Review Notes
Plan Review Notes For Permit 12050398
Permit Number 12050398
Review Stop E
Sequence Number 1
Notes
Date Text
2012-05-30 12:51:4312050398
 477 S. ROSEMARY AVE #320-328
  
 VERIFY THE WORKING CLEARANCES IN THE ELECTRICAL
 EQUIPMENT ROOMS ARE ADEQUATE FOR THE NEW EQUIPMENT. NEC
 110.26
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC
 110.9, 110.10
  
 PLANS ARE UNCLEAR AS TO WIRING METHODS PROPOSED WITHIN
 THE IT ROOM - 320B. IS IT INTENDED THAT THIS ROOM BE
 TREATED AS AN INFORMATION TECHNOLOGY EQUIPMENT ROOM
 WITH A DISCONNECTING MEANS, RAISED FLOORS AND RATED
 WALLS? NEC ARTICLE 645
  
 VERIFY THE ILLUMINATION AND BRIGHTNESS IN THE
 CLASSROOMS MEETS ENERGY CODE REQUIREMENTS. FBC 443.3.7
  
 PROVIDE A SEPARATE PERMIT AND PLANS FOR THE IT ROOM
 FIRE SUPPRESSION SYSTEM
  