2012-05-18 13:00:27 | BUILDING PLAN REVIEW |
| PERMIT: 12050138 |
| ADD: 477 S ROSEMARY # 320 |
| CONT: STRATICON |
| TEL: (561)927-1845 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SHEET A-1 & LS-1 INDICATE THE OCCUPANCY AS A |
| BUSINESS OCCUPANCY, THIS IS CORRECT FOR EDUCATIONAL |
| USAGE ABOVE THE 12TH GRADE. WHERE WE DISAGREE IS HOW WE |
| DETEWRMINE THE OCCUPANT LOAD. THE CODE COMMENTARY IN |
| REGARDS TO FBC-B TABLE 1004.1.1 INDICATES THAT ALTHOUGH |
| THIS IS CLASSIFIED AS A BUSINESS OCCUPANCY WE STILL GO |
| TO TABLE 1004.1 FOR THE INTENDED USAGE. I BELIEVE THE |
| OPEN LAB SHOULD BE TAKEN WITH THE SQUARE FOOTAGE FOR |
| SHOPS AND VOCATIONAL TRAINING ROOMS OR (50 NET), THIS |
| ROOM IS APPROX 1027 SQ FT OR AN OCCUPANT LOAD OF |
| 21OCCUPANTS THE OTHER AREA OF DISCREPANCY IS THE |
| CLASSROOM 320H WHICH IS A CLASSROOM OR (20 NET) THE |
| ROOM SIZE BEING APPROX. 800 SQ FT OR AN OCCUPANT LOAD |
| OF 40. |
| |
| THE BREAK ROOM AND CRITIQUE LOUNGE AREAS SHOULD BE |
| TAKEN AT 15 SQ FT PER OCCUPANT (NET) AND THE OFFICES AS |
| 100 SQ FT PER OCCUPANT.(GROSS) PER TABLE 1004.1.1. THE |
| NET CALCULATION ALLOWS THE DESIGNER TO FIGURE THE |
| OCCUPANT LOAD TO THE ACTUAL OCCUPIED FLOOR AREAS. THE |
| AREAS USED FOR PERMANENT BUILDING COMPONENTS, SUCH AS |
| WALLS, FIXED EQUIPMENT, THICKNESSES OF WALLS, |
| CORRIDORS, RESTROOMS, MECHANICAL ROOMS, AND CLOSETS, IS |
| NOT TO BE INCLUDED IN NET FLOOR AREA, SEE 2010 CODE |
| COMMENTARY UNDER TABLE 1004.1.1. |
| |
| PLEASE NOTE THAT THE TOTAL OCCUPANT LOAD MAY STILL BE |
| ABOVE 49 OCCUPANTS WHEN THE NET AREAS REDUCED AREAS ARE |
| REMOVED FROM THE EQUATION. IF SO THE TWO REMOTE EGRESS |
| OPENINGS WILL MEET THE 2010 FBC-B TABLE 1015.1 AND |
| 1015.2.1 DOORWAYS TO BE 1/3 THE DIAGONAL DISTANCE |
| APART. |
| |
| 2) 2010 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE |
| PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY |
| OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| |
| 3) THE PLANS INDICATE ALL EXIT DOORS SWINGING INTO THE |
| CORRIDOR, PLEASE PROVIDE TYPE OF DOORS AND FIRE RATINGS |
| NO DOOR SCHEDULE WAS PROVIDED. 2010 FBC-B TABLE 715.4. |
| |
| 4) PLEASE PROVIDE CODE COMPLIANCE FOR THE FRONT ENTRY |
| DOUBLE DOORS, 2010 FBC-B1008.1.9.3.(3). |
| |
| 5) PLEASE PROVIDE THE TYPE OF LATCHING MECHANISM TO BE |
| INSTALLED ON THE EGRESS DOORS? 2010 FBC-B 1008. |
| |
| 6) NO DETAILS OF HANDICAPPED RESTROOMS WERE SUBMITTED |
| UNDER THE FIRST PLAN REVIEW. 2010 FBC-B |
| 106.3.5.1.1(10)* |
| |
| 7) THERE ARE AREAS THAT DO NOT INDICATE USE OF ROOMS |
| WITH BI-FOLD DOORS AND AREA WITH JUST A HEADER |
| INDICATED? 106.1.2 ADITIONAL INFORMATION REQUIRED? |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |