2012-05-14 13:06:47FIRE DEPARTMENT REVIEW ***APPROVED***
  
 1. FOR SYSTEM PRESSURES EXCEEDING 100 PSI, PENDENT
 SPRINKLERS SHALL BE PROTECTED FROM UPWARD MOVEMENT.
 HANGERS SHALL BE LOCATED WITHIN 12-INCHES OF THE DROP
 ELBOW. INDICATE THE HANGER TYPE OR METHOD TO BE USED
 FOR RESTRAINING UPWARD MOVEMENT.
 2. INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE FOR
 THIS FLOOR.
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6722
  