Plan Review Notes
Plan Review Notes For Permit 12050356
Permit Number 12050356
Review Stop B
Sequence Number 1
Notes
Date Text
2012-05-16 08:47:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE ENGINEERING FROM PERMIT #07040095 IS FOR FBC
 2004 CODE, AND WAS DESIGNED TO ASCE7-02 140MPH EXPOSURE
 C. FBC 2010, CORRECT EXPOSURE CLASSIFICATION IS NOW
 EXPOSURE D PER FBC 1609.4.3; NEW ENGINEERING REQUIRED
 AS THE BUILDING EXCEEDS 60' IN HEIGHT, SEE FBC
 1609.1.1.
  
 2. THE PRODUCT APPROVAL PROVIDED IS EXPIRED. PLEASE
 SUBMIT CURRENT VALID FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL OR MIAMIDADE NOA, FAC9N-3.
  
 3. WHEN RESUBMITTING, CIRCLE APPLICABLE DETAILS AND
 FASTENING IF ALL OPTIONS DO NOT COMPLY WITH THE DESIGN
 PRESSURES SPECIFIED BY THE ENGINEER (SEE #1).
  
 4. OWNER BUILDER PERMITS NOT ALLOWED FOR CONDOMINIUMS,
 SEE FLORIDA STATUTE 489.103. THE EXEMPTION APPLIES TO
 ONE AND TWO FAMILY DWELLINGS AND COMMERCIAL BUILDINGS.
 AN APPLICATION BY A CONTRACTOR LICENSED FOR THIS SCOPE
 OF WORK IS REQUIRED.
  
  
  