Plan Review Notes For Permit 12050356 |
Permit Number |
12050356 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-05-16 08:47:56 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. THE ENGINEERING FROM PERMIT #07040095 IS FOR FBC | | 2004 CODE, AND WAS DESIGNED TO ASCE7-02 140MPH EXPOSURE | | C. FBC 2010, CORRECT EXPOSURE CLASSIFICATION IS NOW | | EXPOSURE D PER FBC 1609.4.3; NEW ENGINEERING REQUIRED | | AS THE BUILDING EXCEEDS 60' IN HEIGHT, SEE FBC | | 1609.1.1. | | | | 2. THE PRODUCT APPROVAL PROVIDED IS EXPIRED. PLEASE | | SUBMIT CURRENT VALID FLORIDA STATE OR LOCAL PRODUCT | | APPROVAL OR MIAMIDADE NOA, FAC9N-3. | | | | 3. WHEN RESUBMITTING, CIRCLE APPLICABLE DETAILS AND | | FASTENING IF ALL OPTIONS DO NOT COMPLY WITH THE DESIGN | | PRESSURES SPECIFIED BY THE ENGINEER (SEE #1). | | | | 4. OWNER BUILDER PERMITS NOT ALLOWED FOR CONDOMINIUMS, | | SEE FLORIDA STATUTE 489.103. THE EXEMPTION APPLIES TO | | ONE AND TWO FAMILY DWELLINGS AND COMMERCIAL BUILDINGS. | | AN APPLICATION BY A CONTRACTOR LICENSED FOR THIS SCOPE | | OF WORK IS REQUIRED. | | | | | | |
|