2012-05-22 13:19:34 | 5/23/2012 CONTRACTOR E-MAILED WITH ATTACHMENT CODE |
| COMPLIANT CORK SOUND PROOFING MEETING THE FLAME SPREAD |
| REQUIREMENTS FOR CLASS A MATERIALS 0-25 FLAME SPREAD OF |
| 802.1. |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| ------------------------------------------------------- |
| ------------------------------------------- |
| |
| BUILDING PLAN REVIEW |
| PERMIT:12050318 |
| ADD: 1200 S FLAGLER DR # 201 |
| CONT: FOWLER BUILDING |
| TEL: (772)486-5350 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLANS INDICATE THE USE OF AGGLOMERATED CORK TO BE |
| USED AS A FLOOR INSULATION TO MEET THE SOUND |
| REQUIREMENTS OF FBC-B 1207.3 BUT NO REPORTS WERE FILED |
| INDICATING COMPLIANCE WITH |
| 2010 FBC-B 603.1 (2) EXCEPTION (1) INSULATION PLACED |
| BETWEEN TWO LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT |
| AN INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A |
| FLAME SPREAD INDEX OF NOT MORE THAN 100. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |