2012-05-18 14:24:34PLANS DENIED
 1 PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3 FBC
 (M) 2010.
 2 REFER TO SECTION 503.2.1 CALCULATION OF HEATING AND
 COOLING LOADS
 2010 FLORIDA ENERGY CODE.