2012-05-29 10:35:57 | 2465 MERCER AVENUE - SUITE #106 & #107 |
| PERMIT #12050220 |
| (SEE ALSO PERMIT #12050218 FOR SUITE #105) |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH |
| FLORIDA AMENDMENTS SHOULD BE REFERENCED IN THE CODE |
| LIST. |
| |
| ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL |
| DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| PLANS DO NOT INDICATE THE SCOPE OF WORK FOR THE FIRE |
| SPRINKLER SYSTEM. ANY RESIDENTIAL TYPE SPRINKLERS WOULD |
| NEED TO BE REPLACED WITH COMMERCIAL STYLE SPRINKLERS. |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE |
| ALARM SYSTEM. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| ALL EXTERIOR DOORS NOT FUNCTIONING AS EXITS SHALL BE |
| PERMANENTLY MARKED AND CLEARLY INDICATED AS, "NOT AN |
| EXIT." |
| |
| SHEET A-2: PROVIDE FIRE ALARM NOTIFICATION APPLIANCE IN |
| CONFERENCE ROOM #2 AND IN HALLWAY NEAR BREAK ROOM/COPY |
| ROOM. |
| |
| SHEET A-3: PROVIDE EMERGENCY LIGHTING FOR EXIT PATH IN |
| MTC ROOM. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |