2012-06-22 11:36:03 | 2465 MERCER AVENUE - SUITE #105 | | PERMIT #12050218 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | REPEAT COMMENT: ALL DEMOLITION OR CONSTRUCTION AREAS | | SHALL HAVE "NO SMOKING" SIGNS POSTED. | | | | REPEAT COMMENT: ALL EXTERIOR DOORS NOT FUNCTIONING AS | | EXITS SHALL BE PERMANENTLY MARKED AND CLEARLY INDICATED | | AS, "NOT AN EXIT." | | | | REPEAT COMMENT: SHEET A-2: PROVIDE FIRE ALARM | | NOTIFICATION APPLIANCE IN CONFERENCE ROOM #2 AND IN | | HALLWAY NEAR BREAK ROOM/COPY ROOM. | | NEW COMMENT: ALL THE FIRE ALARM NOTIFICATION APPLIANCES | | ORIGINALLY SHOWN ON SHEET A-2 ARE NO LONGER SHOWN. | | | | IN ORDER TO ISSUE A GENERAL BUILDING PERMIT, THE FIRE | | ALARM AND FIRE SPRINKLER SCOPE OF WORK WOULD NEED TO BE | | SHOWN OR DESCRIBED ON THE DESIGN DOCUMENTS. AFTER THE | | GENERAL BUILDING PERMIT HAS BEEN ISSUED, THE | | SUB-CONTRACTORS WILL NEED TO SUBMIT SHOP DRAWINGS (FIRE | | ALARM AND FIRE SPRINKLER) FOR SPECIFIC SUB-PERMITS. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE |
|