Plan Review Notes For Permit 12050218 |
Permit Number |
12050218 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-05-11 14:49:21 | FBC PLUMBING 2010 | | FBC ACCESSIBILITY 2010 | | REVIEW #1 | | DENIED: | | | | 1. SHEET A-1 SHOWS RESTROOMS 5'-7" WIDE | | FBC ACCESSIBILITY 2010 - 604.3.1 AND 604.3.2 REQUIRE A | | 5' CLEAR SPACE FOR THE WATER CLOSET WITH NO OTHER | | FIXTURES WITHIN THAT SPACE. | | | | 2. SHEET A-5 SHOWS A SINK ATTACHED TO A WET VENT | | SYSTEM. THE SINK IS REQUIRED TO CONNECT DOWNSTREAM OF | | THE WET VENTED RESTROOM. | | FBC PLUMBING 909.1 HORIZONTAL WET VENT PERMITTED. ANY | | COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS | | LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE | | VENTED BY A HORIZONTAL WET VENT.....ANY ADDITIONAL | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL | | WET VENT. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | | | | | | | | | |
|