Plan Review Notes
Plan Review Notes For Permit 12050131
Permit Number 12050131
Review Stop M
Sequence Number 1
Notes
Date Text
2012-05-07 08:55:012007 FBC W/2009 REVISIONS
  
 REVISION DENIED BY MECHANICAL
  
 1) THE REVISION THAT WAS SUBMITTED IS ON PLAN SHEET 4.
 SHEET 4 OF THE APPROVED PLANS IS THE PROPOSED FLOOR
 PLAN AND THE PLUMBING PLAN. THE APPROVED MECHANICAL
 PLANS ARE ON SHEET 9. PLEASE SUBMIT THE PROPOSED
 MECHANICAL REVISIONS ON SHEET 9. CITY AMENDMENTS
 106.1.2
  
 2) THE APPROVED MECHANICAL PLAN ON SHEET ARE SIGNED AND
 SEALED BY THE ENGINEER, LUIS LOPEZ. FLORIDA STATUTE FS
 471 REQUIRES THE REVISED PLANS ARE REQUIRED TO BY
 SIGNED AND SEALED BY HIM.
  
 3) THE REVISED PLAN DOES NOT SHOW THE LOCATIONS OF
 CONDENSING UNITS AND DISCONNECTS. FBC M1401
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]