Plan Review Notes
Plan Review Notes For Permit 12050072
Permit Number 12050072
Review Stop B
Sequence Number 1
Notes
Date Text
2012-05-08 07:46:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SHEET T, PROJECT DATA, STATES THAT THE 2ND FLOOR IS
 A SINGLE TENANT. OUR RECORDS SHOW THAT THERE ARE MORE
 THAN ONE TENANT ON THIS FLOOR, PLEASE EITHER EXPLAIN OR
 REVISE NOTE, FBC 709.1(6).
  
 2. GOVERNING CODE CHANGED ON 3/15/2012 TO FBC 2010;
 PLEASE REVISE PROJECT DATA AND REFERENCE STANDARDS AND
 ANY OTHER NOTES AS APPLICABLE; FS 553.73.
  
 3. A2, TENANT SEPARATION WALL DOES NOT APPEAR CONTINOUS
 AT OFFICE 101, SHOWS FIRE RATED WALLS TERMINATING AT
 WHAT APPEARS TO BE A COLUMN. PROVIDE A DETAIL TO SHOW
 HOW FIRE RESISTANCE WILL BE MAINTAINED AT THIS
 LOCATION, FBC 709.1(6).
  
 4. SPECIFY HEAD OF WALL DETAIL FOR THE NEW FIRE RATED
 WALLS, FBC 709.4.
  