Plan Review Notes For Permit 12050072 |
Permit Number |
12050072 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-05-08 07:46:05 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. SHEET T, PROJECT DATA, STATES THAT THE 2ND FLOOR IS | | A SINGLE TENANT. OUR RECORDS SHOW THAT THERE ARE MORE | | THAN ONE TENANT ON THIS FLOOR, PLEASE EITHER EXPLAIN OR | | REVISE NOTE, FBC 709.1(6). | | | | 2. GOVERNING CODE CHANGED ON 3/15/2012 TO FBC 2010; | | PLEASE REVISE PROJECT DATA AND REFERENCE STANDARDS AND | | ANY OTHER NOTES AS APPLICABLE; FS 553.73. | | | | 3. A2, TENANT SEPARATION WALL DOES NOT APPEAR CONTINOUS | | AT OFFICE 101, SHOWS FIRE RATED WALLS TERMINATING AT | | WHAT APPEARS TO BE A COLUMN. PROVIDE A DETAIL TO SHOW | | HOW FIRE RESISTANCE WILL BE MAINTAINED AT THIS | | LOCATION, FBC 709.1(6). | | | | 4. SPECIFY HEAD OF WALL DETAIL FOR THE NEW FIRE RATED | | WALLS, FBC 709.4. | | |
|