Plan Review Notes For Permit 12050064 |
Permit Number |
12050064 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-05-08 09:06:50 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | 2010 FBC. | | | | 1- FLAT ROOF: PLEASE PROVIDE SIGNED AND SEALED RAS 117 | | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON | | LAST PAGE OF NOA 11-0415.15 SUBMITTED. | | NEED RAS 117 CALCULATIONS TO MEET THE DESIGN PRESSURES | | REQUIRED BY SEC. R301.2.1.4.3. | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | TAKE INTO CONSIDERATION THAT THIS BUILDING IS LOCATED | | ON EXPOSURE "C". | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|