Plan Review Notes For Permit 12050036 |
Permit Number |
12050036 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2012-06-07 17:09:56 | PLEASE REVISE THE INSTALLATION SHEDULE. | | | | SHUTTER TO GLASS SEPARATION - 4 1/2" CIRCLED ON PRODUCT | | APPROVAL SHEET 5 (SEE ATTACHED), BUT 3 1/2" PROPOSED. | | | | SEE SHEET 6, ANCHOR SPACING CIRCLED BUT NOT CONSISTENT | | WITH SPANS/SPACING ON THE INSTALLATION SHEDULE. A | | COUPLE EXAMPLES: | | | | OPENING 1, TOP (CONNECTION TYPE 1) 60.3 PSF, 10`.2" | | SPAN, NEED TO USE 11' ROW AND 70PSF COLUMN, 4" | | REQUIRED. | | BOTTOM, 5.5" REQUIRED FOR CONNECTION TYPE 6 | | OPENINGS 2&3, 72.5PSF, 7.5' SPAN, 9" PROPOSED, NEED TO | | USE 80PSF AND 8' ROW, CANNOT USE. | | | | FIRST SUBMITTAL USED LOWER PRESSURES. SECOND SUBMITTAL | | HAS HIGHER PRESSURES PROPOSED. IT APPEARS THAT YOU ARE | | USING V(ULT) PRESSURES WITHOUT CONVERTING TO V(ASD) FOR | | USE WITH PRODUCT APPROVALS. IF YOU WOULD LIKE, YOU CAN | | USE FBC RESIDENTIAL TABLE 301.2(2) TO CALCULATE EACH | | OPENING OR YOU CAN USE +37.9/-50.7 "WORST CASE" (ZONE | | 5, 10SF, 15MRH, EXPOSURE C). | | | | SAMANTHA HILL | | 561-805-6724 | | [email protected] | | |
|