2012-05-29 17:31:14****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. OK
  
 2. 9" SPACING DOES NOT MEET MINIMUMS IN PRODUCT
 APPROVAL FOR OPENINGS 8' AND GREATER, SEE SHEET 6,
 CONNECTION TYPE 1.
  
 ANCHOR SPACING FOR OPENINGS 5 THROUGH 8 WERE LEFT
 BLANK, PLEASE REVISE TO SHOW COMPLIANCE WITH FBC
 RESIDENTIAL 301.1, WIND.
  
 3. OK
  
 4. PLEASE INCLUDE INFORMATION REGARDING TYPE OF
 INSTALLATION; KNUCKLE OR LOCK/CENTERMATES IN ORDER TO
 DETERMINE SHUTTER GLASS SEPARATION REQUIRED, SEE SHEET
 5 OF PRODUCT APPROVAL.
  
 WIND ZONE 3 WAS MARKED ON PRODUCT APPROVAL, WEST PALM
 BEACH IS IN WIND ZONE 4 PER FBC RESIDENTIAL
 301.2.1.2.1. FIRST SUBMITTAL HAD A 4.5" SHUTTER GLASS
 SEPARATION BUT WAS REDUCED TO 3" ON THE SECOND
 SUBMITTAL. 3" DOES NOT COMPLY WITH THE TWO DIFFERENT
 OPTIONS ON SHEET 5.
 PLEASE PROVIDE REQUESTED INFORMATION (KNUCKLE OR
 CENTERMATE) AND REVISE INSTALLATION SCHEDULE.
  
  
  