Plan Review Notes For Permit 12040711 |
Permit Number |
12040711 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-05-07 10:28:16 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. THE CONSTRUCTION TRAILERS WERE NOT PERMITTED AS | | UNINHABITABLE BUILDINGS. THEY WERE REQUIRED TO MEET | | ACCESSIBLITY AND WIND DESIGN TO 140MPH EXPOSURE C. | | REVISE THE WIND DESIGN CRITERIA TO ASCE7-05 140MPH | | EXPOSURE C (LINKED TO THE MASTER PERMIT) OR ASCE7-10 | | EXPOSURE C 166MPH MINIMUM. | | | | 2. FBC 1003.6, MEANS OF EGRESS CONTINUITY, IT APPEARS | | THAT THE THREE EXIT DOORS ARE TO BE BLOCKED BY PANELS, | | NOT PERMITTED IN THE CODE. | | | | 3. IF DESIGNED TO ASCE7-05 AND LINKED TO MASTER, | | PROVIDE FBC2007 PRODUCT APPROVALS, FAC9N-3. | | | | 4. REGARDING THE INSTALLATION SCHEDULE, PLEASE CORRECT | | THE FOLLOWING IN ORDER TO SHOW COMPLIANCE WITH FBC | | 1609.1.4: | | | | SHUTTER MOUNTING CONNECTION TYPE TO CORRELATE WITH THE | | ANCHOR CHARTS (FOR INSTANCE, 1 TOP, 2 BOTTOM; SEE SHEET | | 7). | | | | SEE SHEET 1 OF 10, NOTE 1, THE PRODUCT SUBMITTED IS FOR | | INSTALLATION IN WIND ZONES 1 - 3. FBC2010 PUT WEST PALM | | BEACH IN WIND ZONE 4, FBC 1609.1.2.4. | | |
|