Plan Review Notes
Plan Review Notes For Permit 12040711
Permit Number 12040711
Review Stop B
Sequence Number 1
Notes
Date Text
2012-05-07 10:28:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE CONSTRUCTION TRAILERS WERE NOT PERMITTED AS
 UNINHABITABLE BUILDINGS. THEY WERE REQUIRED TO MEET
 ACCESSIBLITY AND WIND DESIGN TO 140MPH EXPOSURE C.
 REVISE THE WIND DESIGN CRITERIA TO ASCE7-05 140MPH
 EXPOSURE C (LINKED TO THE MASTER PERMIT) OR ASCE7-10
 EXPOSURE C 166MPH MINIMUM.
  
 2. FBC 1003.6, MEANS OF EGRESS CONTINUITY, IT APPEARS
 THAT THE THREE EXIT DOORS ARE TO BE BLOCKED BY PANELS,
 NOT PERMITTED IN THE CODE.
  
 3. IF DESIGNED TO ASCE7-05 AND LINKED TO MASTER,
 PROVIDE FBC2007 PRODUCT APPROVALS, FAC9N-3.
  
 4. REGARDING THE INSTALLATION SCHEDULE, PLEASE CORRECT
 THE FOLLOWING IN ORDER TO SHOW COMPLIANCE WITH FBC
 1609.1.4:
  
 SHUTTER MOUNTING CONNECTION TYPE TO CORRELATE WITH THE
 ANCHOR CHARTS (FOR INSTANCE, 1 TOP, 2 BOTTOM; SEE SHEET
 7).
  
 SEE SHEET 1 OF 10, NOTE 1, THE PRODUCT SUBMITTED IS FOR
 INSTALLATION IN WIND ZONES 1 - 3. FBC2010 PUT WEST PALM
 BEACH IN WIND ZONE 4, FBC 1609.1.2.4.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved