Text |
2012-04-30 15:06:44 | BUILDING PLAN REVIEW | | PERMIT:12040652 | | ADD: 7422 S DIXIE HWY | | CONT: LANTANA CONSTRUCTION | | TEL: (561)312-3600 | | | | 2010 FLORIDA BUILDING CODE W | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) SHEET 1 PLEASE SEE NEW 2010 ACCESSIBILITY CODE AND | | FIGURE 604.8.1.6 WHEELCHAIR ACCESSIBLE TOILET | | COMPARTMENT IN NEW CONSTRUCTION. THE MINIMUM DIMENSIONS | | ARE 84 1/2 " X 60" WITH THE WATERCLOSET AND LAV LOCATED | | ON THE 84 1/2" WALL. THE LAV CAN NOT OVER LAP INTO THE | | CLEAR FLOOR SPACE FOR THE WATER CLOSET.SEE FIGURE | | 604.3.1. | | | | 2) NEW TO THE 2010 ACCESSIBILITY CODE GRAB BARS ARE NO | | LONGER MEASURED TO THE CENTER LINE BUT TO THE TOP OF | | THE BAR PER SECTION 604.8.1.5/ 609.4 THE TOP OF THE | | GRIPPING SURFACE 33 INCHES MINIMUM AND 36 INCHES | | MAXIMUM. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CONSTRUCTION SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | |
|