2012-05-04 12:11:08 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| 1. THIS PARCEL IS LOCATED IN EXPOSURE C, FBC |
| RESIDENTIAL 301.2.1.4.3. |
| |
| 2. SLIDING WINDOW DETAIL SHOWS A BEVELED BUCK. SEE FBC |
| 1715.5.4.2, BUCKS SHALL EXTEND BEYOND THE INTERIOR FACE |
| OF THE WINDOW FRAME UNLESS OTHERWISE TESTED. |
| |
| 3. PLEASE REVISE CODE REFERENCES; ASCE7 REFERENCE IS |
| OUTDATED. PLEASE CORRECT THE FOLLOWING: WIND SPEED (FBC |
| R301.2(4), MINIMUM OF 170MPH), EXPOSURE CLASSIFICATION, |
| GOVERNING CODE, ASCE7 REFERENCE (FBC R301.2.1.1) AND |
| OTHER INFORMATION (SUCH AS DESIGN PRESSURES) AS |
| APPLICABLE. |
| |
| 4. SPECIFY DESIGN PRESSURE REQUIREMENT FOR THE NEW |
| OPENING, FBC R 301.2.1. BOTH INTERIOR AND CORNER ZONE |
| PRESSURES FOR 30 AND 40 SF WERE PROVIDED FOR ONE |
| OPENING, WITH A DIMENSION STATING WHAT THE CORNER |
| DISTANCE IS, BUT NO DIMENSION ON THE DETAIL TO SHOW |
| WHETHER THIS IS ZONE 4 OR 5 AND NO DIMENSION ON THE |
| PLAN FOR THE WINDOW. ENGINEER'S INTENT NOT CLEAR. |
| PLEASE SPECIFY A DESIGN PRESSURE FOR THE ONE OPENING OR |
| CLARIFY SCOPE OF WORK. |
| |
| 5. IMPACT PROTECTION REQUIRED, FBC R 301.2.1.2. IF |
| SHUTTERS ARE PROPOSED RATHER THAN IMPACT GLASS, PLEASE |
| SUBMIT PRODUCT APPROVALS AND COMPLETE THE SAMPLE |
| INSTALLATION SCHEDULE OR PROVIDE ALL INFORMATION TO |
| SHOW CODE COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC |
| R301, FBC1609. TWO SETS REQUIRED. THIS FORM IS |
| AVAILABLE IN THE LOBBY OR ON THE INTERNET AT |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| INSTALLATION.PDF |
| |
| 6. FBC R 703.6.3, BOND BREAK REQUIRED, PLEASE REVISE |
| EXTERIOR WALL FILL IN DETAIL. |
| |
| |