2012-05-04 15:19:26****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. STEEL SUBSTRATE IS NOT AN OPTION IN THE PRODUCT
 APPROVAL, PLEASE PROVIDE SITE SPECIFIC ENGINEERING.
  
 2. A 1" EDGE DISTANCE IS NOT PERMITTED FOR CONCRETE.
 ALTHOUGH IT'S A TRAPPED OPENING, EDGE DISTANCE MUST BE
 MAINTAINED SO THE CONCRETE SUBSTRATE IS NOT
 COMPROMISED, SEE SHEET 7. A 1 3/4" MINIMUM EDGE
 DISTANCE IS REQUIRED, SEE "FACTOR" TABLE ON SHEET 13.
 APPLICABLE FACTOR TO BE APPLIED TO ANCHOR SPACING IN
 THE CHART.
  
 3. WHEN RESUBMITTING, PLEASE PROVIDE TWO SETS OF THE
 INSTALLATION SCHEDULE. FAILURE TO PROVIDE TWO SETS MAY
 RESULT IN PERMIT ISSUANCE DELAYS DUE TO TIME
 CONSTRAINTS. A PHOTOCOPY MACHINE IS IN THE LOBBY FOR
 YOUR CONVENIENCE.
  
 4. PLEASE ADVISE AS TO WHICH OPTION IS TO BE USED,
 SYMMETRICAL CENTERMATES OR OPPOSING CENTERMATES, AND
 REVISE SHUTTER TO GLASS SEPARATION IF NECESSARY, SEE
 SHEET 11.
  
 5. PLEASE ADVISE AS TO HOW YOU HAVE DETERMINED DESIGN
 PRESSURES. THE BUILDING MRH APPEARS TO BE HIGHER THAN
 40' AS IT IS FOUR STORIES, PITCHED ROOF. 81.2/-108.7
 ULT = 48.72/-65.22 ASD. PRESSURES PROPOSED RANGE FROM
 -47.99 TO 50.4, APPEAR TOO LOW BASED ON ENGINEERING
 PROVIDED.
  
  