2012-05-14 13:08:39 | ****CORRECTIONS**** |
| ****REVISED COMMENT LIST**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| 1. FAC61G15-23.001, THE SEAL IS TO INCLUDE THE WORD |
| "LICENSE." USE OF THE WORD "CERTIFICATE" HAS NOT BEEN |
| ACCCEPTABLE TO FBPE EFFECTIVE JANUARY 1, 2006 PURSUANT |
| TO A RULE CHANGE EFFECTIVE FEBRUARY 5, 2004. |
| |
| 2. FAC61G15-23.002(1), ENGINEER SHALL SIGN BY HAND THE |
| LICENSEE'S HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT |
| ACCEPTABLE). IT APPEARS THAT THE SIGNATURE ON THE TWO |
| SETS OF PLANS ARE PHOTOCOPIES. |
| |
| 3. PROPOSED IMPROVEMENT'S RESISTANCE TO DESIGN |
| PRESSURES, UPLIFT AND LATERAL, ARE NOT CLEAR. THE PLAN |
| STATES THAT THE SOLAR UNITS ARE NOT COMPONENTS AND |
| CLADDING, AND REFERS TO A WEBSITE. THE WEBSITE APPEARS |
| TO SPECIFY COMPONENT AND CLADDING PRESSURES. PLEASE SEE |
| FBC RESIDENTIAL 301.2.1.1.3 AS IT APPEARS THAT |
| PRESSURES SHOULD BE DETERMINED USING ROOFTOP STRUCTURES |
| METHOD IN ASCE7-10 CHAPTER 29 RATHER THAN COMPONENTS |
| AND CLADDING ASCE7-10 CHAPTER 30. CALCULATIONS MAY BE |
| REQUIRED. |
| |
| 4. PLAN STATES THAT "COLLECTOR INSTALLATION STANDARD |
| FLUSH W/ROOF" BUT ALSO STATES IN OTHER TEXT THAT THE |
| COLLECTORS CAN BE TILTED. CLARIFY INSTALLATION METHOD |
| AND AMOUNT OF TILT PERMITTED SO THAT COMPLIANCE WITH |
| FBC RESIDENTIAL 301.2.1.1.3, LATERAL LOADS, CAN BE |
| DETERMINED. |
| |
| 5. ENGINEERING PROVIDED IS GENERIC. TO SHOW DEMONSTRATE |
| CODE COMPLIANCE AND TO FACILITATE INSPECTIONS, PLEASE |
| PROVIDE THE FOLLOWING INFORMATION: |
| |
| DISTANCE FROM SOLAR PANEL(S) TO ROOF EDGE AND RIDGE |
| STRAP MATERIAL |
| STRAP ANCHOR SPACING AND FASTENER PROPOSED |
| FLUSH MOUNT OR TILT UP - IF TILT UP, PROVIDE DIMENSION |
| OF RISE |
| |
| 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, VALUE |
| TOO LOW, FBC 108.3. |
| |
| |
| |
| |