2012-04-26 18:33:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC RESIDENTIAL 301.2.1.1, PER ASCE7-10 REVISE THE
 FOLLOWING:
  
 INCLUDE RISK CATEGORY IN DESIGN CRITERIA
 REVISE TO EXPOSURE C
 IF THIS IS RISK CATEGORY 1, WIND SPEED SHOULD BE 152;
 RISK CATEGORY II IS 164.
  
  