Plan Review Notes For Permit 12040590 |
Permit Number |
12040590 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-04-28 22:18:40 | FIRE PLAN REVIEW | | PERMIT #12040590 | | ADDRESS: 100 CLEMATIS STREET | | | | PLANS REVIEWED BY FIRE ***APPROVED*** | | | | | | 1.) TENT SHALL BE OF THE OPEN AREA/NO SIDES TYPE, | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | 2.) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | 3.) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | LOCATIONS. | | | | | | DERRICK L. DANIELS, BATTALION CHIEF | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | (561) 805-6733 | | |
|