2012-05-22 10:59:31 | BUILDING PLAN REVIEW |
| PERMIT: 12040588 |
| ADD:2700 BROADWAY |
| CONT: PKS CONSTRUCTION |
| TEL: (561)704-2394 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SHEET A-1: |
| 1A) SHEET A-1 & A-2 SIGNED AND SEALED DATED 4/19/2012, |
| PLANS ARE DESIGNED UNDER THE 2007 FBC-B. MARCH 15/ 2012 |
| IS THE ADOPTION DATE STATEWIDE FOR THE 2010 FBC-B, |
| PLANS SUBMITTED ON THAT DATE AND LATER FOR FIRST REVIEW |
| ARE TO BE DESIGNED TO THE 2010 FBC. SINCE THIS IS AN |
| ADDITION THE PLANS WILL ALSO BE REVIEWED TO THE 2010 |
| EXISTING BUILDING CODE CHAPTER 10 FOR ADDITIONS AND |
| CHAPTER 11 FOR HISTORIC BUILDINGS. |
| |
| 1B) 2010 EXIST BUILDING CODE 1002.2 PLEASE PROVIDE CODE |
| ANALYSIS FOR BUILDING, MINIMUM BUILDING TYPE, SQUARE |
| FOOTAGE OF EXISTING BUILDING, SPRINKLERED OR NOT AND |
| TYPE OF OCCUPANCY FOR AREA LIMITATIONS. 106.3.5.1.1* |
| MINIMUM COMMERCIAL PLAN REVIEW CRITERIA. |
| |
| 1C) WIND DESIGN CRITERIA IS FOR THE 2007 FBC NOT THE |
| 2010 FBC-B PLEASE REVIEW 1609.1.1. |
| |
| 2) FRONT PORCH ADDITION; |
| 2A) SHEET A2 ROOF FRAMING PLAN FAILS TO IDENTIFY BOTH |
| B-1 CARRYING BEAM ATTACHMENTS TO THE EXISTING |
| STRUCTURE, PART OF THE MWFRS (MAIN WIND FORCE RESITING |
| SYSTEM) PLEASE PROVIDE TYPE OF BUCKET AND ATTACHMENT. |
| 106.1.2* ADTIONAL INFORMATION REQUIRED / |
| 106.3.5.1.1.(8)*. |
| |
| 2B) SHEET A1 FRONT PORCH DETAIL INDICATES THE ROOF |
| JOIST ANCHORING TO BEAM B1 BUT THIS DETAIL NOR THE |
| DETAIL ON A2 PROVIDE THE CANTILVERED ROOF JOIST |
| ATTACHMENT TO BEAM B-1 NOR THE COMMON JOIST THEY ATTACH |
| TOO? PART OF THE MWFRS, 106.3.5.1.1(8)*. |
| |
| 2C) THE SAME DETAIL INDICATES THE ATTACHMENT OF LEDGER |
| TO THE WALL WITH 1/2" BOLTS @ 4'-0" O.C.? PLANS LACK |
| THE TYPE OF ANCHOR TO BE INSTALLED, LENGTH OF ANCHOR, |
| IS THIS ANCHOR GOING TO BE INSTALLED INTO A CONCRETE |
| BEAM, FILLED MASONRY BLOCK BEAM OR EMPTY CONCRETE BLOCK |
| UNITS. |
| |
| 2D) SHEET A-1 FRONT PORCH DETAIL INDICATES THE ROOFING |
| MATERIALS TO BE MODIFIED PEEL AND STICK ROOFING WHERE |
| AS THE ACTUAL PRODUCT APPROVAL IS A GAF RUBEROID |
| MODIFIED BITUMEN ROOF SYSTEM FOR ROOF DECKS WHICH IS |
| CORRECT? IF THE PEEL AND STICK NOTE IS DELETED AND THIS |
| APPROVAL WILL BE INSTALLED THEN PLEASE IDENTIFY WHICH |
| OF THE SUB-SYSTEMS WILL BE APPLIED, PLEASE NOTE THAT IN |
| ROOF ZONES 2 & 3 ENHANCED FASTENING WILL BE REQUIRED |
| WHEN LIMITATION NOTE # 7 APPEARS LIMITATION NOTE # 9 |
| DOES NOT ALLOW FOR ENHANCED FASTENING. |
| |
| 3) BACK PORCH ADDITION, ALL OF THE CONDITIONS LISTED |
| ABOVE ARE THE SAME CONDITIONS FOR THE BACK PORCH |
| ADDITION. |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |