2012-04-25 14:58:461015 GREEN PINE BOULEVARD
 PERMIT #12040571
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO PRODUCT DATA SUBMITTED FOR MANUAL PULL STATIONS. ADD
 PULL STATIONS TO SCOPE OF WORK AND TOTAL JOB VALUE.
  
 THE QUANTITY OF DEVICES INDICATED ON THE PERMIT
 APPLICATION DOES NOT MATCH THE DEVICES SHOWN ON THE
 PLANS.
  
 THE FACP IS NOT INDICATED AS WEATHERPROOF. INDICATE THE
 ENCLOSURE (NEMA) RATING FOR THE FIRE ALARM CONTROL
 PANEL.
  
 THE RISER DIAGRAM SHOWS TWO TELEPHONE LINES. INDICATE
 IF THE FIRE ALARM SYSTEM IS MONITORED OR ONLY INSTALLED
 FOR LOCAL ALARM.
  
 FIRE ALARM PLANS WITH A JOB VALUE GREATER THAN $5,000
 ARE REQUIRED TO BE SIGNED/SEALED BY A PROFESSIONAL
 ENGINEER.
  
 INDICATE THE SOUND PRESSURE LEVEL (DB) TO BE PROVIDED
 AT THE PILLOW IN SLEEPING AREAS.
  
 NOTE:PER FLORIDA ADMINISTRATIVE CODE 69A-48.002, THESE
 RULES APPLY TO BOTH NEW AND EXISTING FIRE ALARM SYSTEMS
 AS OF THE EFFECTIVE DATE OF THE RULE. THOSE SYSTEMS
 WHICH WERE BASED ON PRODUCT AND ENGINEERING PRACTICES
 RECOGNIZED AS BEING ACCEPTABLE AT THE DATE OF
 INSTALLATION BUT ARE NOT IN COMPLIANCE WITH CURRENTLY
 ADOPTED STANDARDS MAY CONTINUE IN USE, PROVIDED THEY
 ARE FUNCTIONAL AND APPROVED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE