2012-04-25 14:58:46 | 1015 GREEN PINE BOULEVARD |
| PERMIT #12040571 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NO PRODUCT DATA SUBMITTED FOR MANUAL PULL STATIONS. ADD |
| PULL STATIONS TO SCOPE OF WORK AND TOTAL JOB VALUE. |
| |
| THE QUANTITY OF DEVICES INDICATED ON THE PERMIT |
| APPLICATION DOES NOT MATCH THE DEVICES SHOWN ON THE |
| PLANS. |
| |
| THE FACP IS NOT INDICATED AS WEATHERPROOF. INDICATE THE |
| ENCLOSURE (NEMA) RATING FOR THE FIRE ALARM CONTROL |
| PANEL. |
| |
| THE RISER DIAGRAM SHOWS TWO TELEPHONE LINES. INDICATE |
| IF THE FIRE ALARM SYSTEM IS MONITORED OR ONLY INSTALLED |
| FOR LOCAL ALARM. |
| |
| FIRE ALARM PLANS WITH A JOB VALUE GREATER THAN $5,000 |
| ARE REQUIRED TO BE SIGNED/SEALED BY A PROFESSIONAL |
| ENGINEER. |
| |
| INDICATE THE SOUND PRESSURE LEVEL (DB) TO BE PROVIDED |
| AT THE PILLOW IN SLEEPING AREAS. |
| |
| NOTE:PER FLORIDA ADMINISTRATIVE CODE 69A-48.002, THESE |
| RULES APPLY TO BOTH NEW AND EXISTING FIRE ALARM SYSTEMS |
| AS OF THE EFFECTIVE DATE OF THE RULE. THOSE SYSTEMS |
| WHICH WERE BASED ON PRODUCT AND ENGINEERING PRACTICES |
| RECOGNIZED AS BEING ACCEPTABLE AT THE DATE OF |
| INSTALLATION BUT ARE NOT IN COMPLIANCE WITH CURRENTLY |
| ADOPTED STANDARDS MAY CONTINUE IN USE, PROVIDED THEY |
| ARE FUNCTIONAL AND APPROVED BY THE AUTHORITY HAVING |
| JURISDICTION. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |