2012-08-20 13:50:25 | UPDATED IN REVIEW # 2 |
| |
| FBC EXISTING BUILDING CODE 2010 |
| FBC ACCESSIBILITY CODE 2010 |
| FBC PLUMBING CODE 2010 REVIEW #1 |
| DENIED: |
| |
| FBC PLUMBING TABLE 403.1 |
| DAY CARE AND EDUCATIONAL OCCUPANCIES REQUIRE DRINKING |
| FOUNTAINS AND A SERVICE SINK. THE SUBMITTED PLAN DOES |
| NOT SHOW THESE FIXTURES (HEALTH DEPT. REGULATIONS ALSO |
| REQUIRE THESE FIXTURES - ARTICLE X #46 & #48). |
| |
| 2. FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO |
| FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| FOUNTAINS. |
| 602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR FLOOR |
| OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A |
| FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE |
| CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| EXCEPTION: A PARALLEL APPROACH COMPLYING WITH 305 SHALL |
| BE PERMITTED AT UNITS FOR CHILDREN'S USE WHERE THE |
| SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND AND IS 3 1/2 INCHES (90 MM) MAXIMUM |
| FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS. |
| |
| |
| ****INFORMATIONAL**** |
| 3. FBC 2012 TABLE 1004.1.1 |
| FROM THE BUILDING REVIEW COMMENTS A CHANGE OF OCCUPANCY |
| - EDUCATIONAL OCCUPANCIES ARE 20 S.F. PER OCCUPANT. THE |
| TOILET FACILITIES SHOWN WOULD BE SUFFICIENT. |
| |
| PLEASE SEE THE HEALTH DEPT. WEB SITE FOR REQUIREMENTS: |
| HTTP://WWW.PBCHD.COM/PDFS/ENVIRONMENTAL/CHILDCARE/PBCHD |
| _RULES_AND_REGULATIONS_GOVERNING_CHILD_CARE_FACILITIES. |
| PDF |
| |
| REVIEW BY |
| LARRY WAGNER |
| CHIEF PLUMBING INSPECTOR |
| PHONE # 805-6692 |
| EMAIL [email protected] |
| FAX # 805-6676 |
| |
| |
| |