2012-04-30 11:21:00 | BUILDING PLAN REVIEW |
| PERMIT: 12040562 |
| ADD: 5600 N FLAGLER # PH102 |
| CONT: L-BOYS BUILDING & DESIGN LLC |
| TEL: (561)346-0543 |
| |
| 2010 FLORIDA BUILDING CODE W/ |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) 106.1.2* ADDITIONAL DATE REQUIRED. THE CONTRACTOR OF |
| RECORD TO TAKE RESPNSIBILITY FOR THE DESIGN OF THE |
| PLANS, PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| LICENSE NUMBER OF YOUR BUSINESS. |
| |
| 2) 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| COMMERCIAL BUILDINGS- |
| 106.3.5 (9) MATERIALS SHALL BE REVIEWED AND SHALL AT A |
| MINIMUM INCLUDE THE FOLLOWING DESIGN CRITERIA: |
| (A) STEEL STUDS, & CEILING JOIST: PROVIDE THE SIZE OF |
| THE CEILING JOIST, GAUGE, SPACING, CLEAR SPAN IF STRONG |
| BACKS ARE GOING TO BE INSTALLED, WHERE AND TYPE OF |
| MATERIAL TO BE |
| INSTALLED IF STRONG BACKS ARE INSTALLED. PLEASE ALSO |
| PROVIDE THE DESIGN CRITERIA FOR DEFLECTION PER FBC-B |
| TABLE 1604.3. 2010 FBC-B TABLE 2508.1 STEEL FRAMING FOR |
| GYPSUM |
| BOARD, & TABLE 2506.2 STEEL STUDS NON LOAD BEARING. |
| |
| B) PLANS DO NOT PROVIDE THE THICKNESS OF DRYWALL TO BE |
| INSTALLED ON THE DROP CEILING THAT IS REPLACING THE |
| REMOVED ACOUSTICAL CEILING. 106.3.5((9) GYPSUM BOARD |
| AND |
| PLASTER. |
| |
| 3) NO ELECTRICAL SHOWN ON PLANS, THE ELECTRICAL |
| CONTRACTOR WILL NEED TO DRAW THEIR OWN ELECTRICAL PLANS |
| AND MEET THE SAME REQUIREMENTS AS THE DESIGNER OF PLANS |
| FOR ELECTRICAL. |
| |