2012-05-21 15:07:00THE NEW PLANS SHOW THE EXISTING ELECTRICAL PANELBOARD
 LOCATED WITHIN A FIRE RATED ASSEMBLY. PLEASE RELOCATE
 THE PANELBOARD OR PROVIDE A DETAIL FOR FIRE STOPPING OF
 THE OPENING TO MAINTAIN THE FIRE RESISTANT RATING. NEC
 300.21
  
 R. LECKY, CBO
 ELECTRIC PLANS EXAMINER