Plan Review Notes
Plan Review Notes For Permit 12040454
Permit Number 12040454
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-04-27 12:07:16330 CLEMATIS STREET - SUITE #112
 PERMIT #12040454
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE ? NFPA 101
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 INDICATE THE EGRESS ROUTE(S) FOR UNIT #111.
  
 THE NEWLY CREATED CORRIDOR IN UNIT #112 CREATES A
 DEAD-END IN EXCESS OF 20 FEET.
  
 A NEW FIRE RATED DOOR IS SHOWN COMMUNICATING BETWEEN
 UNITS #112 AND #113. INDICATE THE PURPOSE OF THIS DOOR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  
  
  