2012-04-23 13:44:11 | BUILDING PLAN REVIEW |
| PERMIT: 12040454 |
| ADD: 330 CLEMATIS ST # 112 |
| CONT: MTC REMODELING INC |
| TEL: (561)719-0725 |
| |
| 2010 FLORIDA BUILDING CODE W/ |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) COVER SHEET: |
| 1A) PLEASE MAKE CORRECTIONS TO THE 2010 FBC-B WHICH WAS |
| ADOPTED AND ENACTED STATE-WIDE MARCH 15/ 2012. |
| |
| 1B) PLEASE PROVIDE THE MINIMUM BUILDING TYPE: |
| 106.3.5.1.1( 3) SEE TABLE 503. |
| |
| 2) PLANS ARE NOT CLEAR THAT IF THE TENANT SEPERATION |
| WALL CONTINUES THROUGH ON THE MEZZANINE LEVEL? IF NOT |
| WHERE WOULD THE SEPERATION BETWEEN THE TWO TENANTS BE |
| LOCATED? |
| |
| 3) PLEASE PROVIDE A SCALE FOR THE NEWLY FORMED |
| CORRIDOR, IT APPEARS TO BE GREATER THAN 20'-0". FBC-B |
| 1017.3. |
| |
| 4) PROVIDE COMPLIANCE WITH ; |
| FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, |
| SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| |
| 5) PLEASE REVIEW THE ACCESSIBILITY REQUIREMENTS FOR THE |
| NEW RESTROOM DOOR AND SIDE APPROACH, FBC -B SEE FIGURE |
| 11-404.2.4.1(H) MINIMUM CORRIDOE WIDTH OF 48". |
| |