2012-04-26 17:28:26 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. CONTRACTOR HAS NOT PERFORMED THE CONVERSION FROM | | V(ULT) TO V(ASD) CORRECTLY. THE DESIGN PRESSURE IS TO | | MULTIPLIED BY .6 PER FBC RESIDENTIAL 301.2.1.7. | | | | 2. THIS PARCEL IS LOCATED IN EXPOSURE D. PLEASE SEE FBC | | RESIDENTIAL 301.2.4.1.3. REVISE DESIGN PRESSURES AND | | DESIGN PRESSURES ACCORDINGLY. | | | | 3. TWO COPIES OF THE SCHEDULE FOR INSTALLATION ARE | | REQUIRED. THERE IS A PHOTOCOPY LOCATED IN THE LOBBY FOR | | YOUR CONVENIENCE. THIS FORM MAY BE FILLED OUT IN | | ADVANCE AND IS AVAILABLE ON OUR WEBSITE: | | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | INSTALLATION.PDF | | | | FAILURE TO PROVIDE TWO COMPLETE SETS OF PERMIT | | DOCUMENTS MAY RESULT IN PERMIT DELAYS. | | | | 4. AS THE SHUTTER TO GLASS SEPARATION DOES NOT MEET THE | | MOST STRINGENT REQUIREMENT ON SHEET 11, PLEASE INDICATE | | THE OPTION PROPOSED. | | | | |
|