Plan Review Notes For Permit 12040374 |
Permit Number |
12040374 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-05-03 09:54:25 | PLANS DENIED | | 1) PLANS SHOW DUCT DETECTOR ON RETURN AIR. REFER TO | | SECTION | | 606.2.1 SUPPLY AIR SYSTEMS. 2010 FBC (M) | | 2) PROVIDE A DETAIL BY THE ENGINEER FOR CONDENSER STAND | | TO ROOF TIEDOWN AND CONDENSER TO STAND TIEDOWN ON THE | | PLANS. | | 3) HOODS,COOLERS AND FREEZERS REQUIRE SEPARATE | | APPLICATION | | PLANS AND PERMIT | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] | | |
|