Plan Review Notes
Plan Review Notes For Permit 12040374
Permit Number 12040374
Review Stop E
Sequence Number 1
Notes
Date Text
2012-05-01 08:49:1812040374
 7750 OKEECHOBEE BLVD.
 INTERIOR BUILDING OUT FOR JJ
  
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 505.5.3
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 FBC505.1, 505.2
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER