Plan Review Notes For Permit 12040352 |
Permit Number |
12040352 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-04-20 13:58:05 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FOR THE SHUTTER, COMPLETE THE SAMPLE INSTALLATION | | SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE | | COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301, | | FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN | | THE LOBBY OR ON THE INTERNET AT | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | INSTALLATION.PDF | | | | 2. SHUTTER INSTALLATION IS NOT WITHIN THE SCOPE OF THIS | | SPECIALTY LICENSE. THIS WORK MUST BE SUBCONTRACTED. | | | | 3. SHUTTER PRODUCT APPROVAL HAS A "PENDING" STATUS; | | PLEASE PRINT CURRENT COVER SHEET IF APPROVED AT THIS | | TIME. OTHERWISE, A VALID CURRENT FLORIDA STATE OR LOCAL | | PRODUCT APPROVAL IS REQUIRED. | | | | 4. PROPOSED MULLION INSTALLATION NOT CLEAR. TWO | | DIFFERENT LENGTHS ARE CIRCLED ON SHEET 7, AND ONE ON | | SHEET 8, BUT IT APPEARS THAT ONLY ONE SIZE IS TO BE | | INSTALLED, 63", AND THIS SIZE IS NOT CIRCLED. PROVIDE | | CALCULATION (ANCHOR CAPACITY ADJUSTMENT FORMULA) ADVISE | | WHICH OPTIONS (MULLION TYPE, ANCHOR, SUBSTRATE) ARE | | PROPOSED. | | | | | | |
|