2012-04-20 13:58:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. FOR THE SHUTTER, COMPLETE THE SAMPLE INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301,
 FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN
 THE LOBBY OR ON THE INTERNET AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. SHUTTER INSTALLATION IS NOT WITHIN THE SCOPE OF THIS
 SPECIALTY LICENSE. THIS WORK MUST BE SUBCONTRACTED.
  
 3. SHUTTER PRODUCT APPROVAL HAS A "PENDING" STATUS;
 PLEASE PRINT CURRENT COVER SHEET IF APPROVED AT THIS
 TIME. OTHERWISE, A VALID CURRENT FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL IS REQUIRED.
  
 4. PROPOSED MULLION INSTALLATION NOT CLEAR. TWO
 DIFFERENT LENGTHS ARE CIRCLED ON SHEET 7, AND ONE ON
 SHEET 8, BUT IT APPEARS THAT ONLY ONE SIZE IS TO BE
 INSTALLED, 63", AND THIS SIZE IS NOT CIRCLED. PROVIDE
 CALCULATION (ANCHOR CAPACITY ADJUSTMENT FORMULA) ADVISE
 WHICH OPTIONS (MULLION TYPE, ANCHOR, SUBSTRATE) ARE
 PROPOSED.
  
  
  