Plan Review Notes
Plan Review Notes For Permit 12040332
Permit Number 12040332
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-16 19:31:16RESPONSE TO REQUEST FOR CONSIDERATION UNDER 2010 FBC
 SECTION 104.11 ALTERNATIVE MATERIAL, DESIGN AND METHODS
 OF CONSTRUCTION AND EQUIPMENT.
  
 THIS REVIEW IS TO GIVE CONSIDERATION TO THE PROPOSED
 USE OF OLYBOND 500 ADHESIVE FOR ATTACHMENT OF POLYISO
 INSULATION PANELS TO STEEL DECK IN LIEU OF MECHANICAL
 FASTENING USING DRILL-TEC FASTENERS AND 3 INCH DIA.
 DRILL-TEC STEEL PLATES AS SPECIFIED IN MIAMI-DADE NOA#
 10-0125.05:
  
 ** EITHER PROVIDE A LETTER FROM CAMPANY ROOFING
 AGREEING TO PROVIDE PULL TESTS SHOWING RESISTANCE TO A
 DESIGN UPLIFT OF -115 PSF OR PROVIDE THE FOLLOWING
 DOCUMENTATION:
  
 IF ABOVE-MENTIONED SITE SPECIFIC PULL TESTS WILL NOT BE
 PERFORMED PLEASE PROVIDE A LETTER FROM OMG, INC., AS
 MANUFACTURER OF OLYBOND 500, TO ADDRESS THE FOLLOWING:
  
 1) COMPATIBILITY - PAGE 2 OF MIAMI-DADE NOA#
 07-1120.05, UNDER SCOPE STATES THAT THE NOA IS LIMITED
 ONLY TO THOSE ROOF ASSEMBLIES WHERE OLYBOND 500 IS
 SPECIFICALLY LISTED AS AN ACCEPTED COMPONENT. PLEASE
 PROVIDE A LETTER FROM OMG, INC., AS MANUFACTURER OF
 OLYBOND 500 STATING THAT IT IS SUITABLE FOR USE WITH
 ENERGYGUARD RA POLYISO INSULATION PANELS.
  
 2) ADHESION - RIZA ALTAN, P.E., LETTER DATED 4/2/12,
 STATES THAT THE TENSILE RESISTANCE OF OLYBOND 500
 ADHESIVE "ON STEEL SURFACES IS 9 PSI". HOWEVER PAGE 2
 OF MIAMI-DADE NOA# 07-1120.05, UNDER PRODUCT
 DESCRIPTION SIMPLY STATES THAT THE TENSILE STRENGTH OF
 OLYBOND 500 IS 9 PSI, WITH NO REFERENCE TO ADHESION TO
 STEEL. THE TENSILE STRENGTH OF THE MATERIAL IS A
 MEASURE OF ITS ABILITY TO RESIST FORCE IN TENSION, IT
 IS NOT A STATEMENT OF ITS ABILITY TO ADHERE TO STEEL OR
 ANY OTHER SUBSTRATE. THE ABILITY OF OLYBOND 500 TO
 ADHERE TO STEEL IS NOT SPECIFICALLY MENTIONED IN THE
 NOA. PLEASE PROVIDE A LETTER/REPORT FROM OMG, INC., AS
 MANUFACTURER OF OLYBOND 500 GIVING RESULTS OF PULL
 TESTS WITH STEEL USED AS THE SUBSTRATE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]
  
  
  
  
  
2012-04-13 10:38:09SENT TO ROBERT BROWN'S DESK FOR LOCAL PRODUCT APPROVAL
 REVIEW.