Plan Review Notes
Plan Review Notes For Permit 12040320
Permit Number 12040320
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-20 14:27:27****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. DESIGN PRESSURES APPEAR TOO LOW. EXPOSURE C, 15 MRH,
 10 SF OPENING (WORST CASE) ZONE 4, DESIGN PRESSURES
 SHOULD BE +37.9 / -41.1; -36.7 PROPOSED. IT IS NOT
 CLEAR HOW YOU HAVE DETERMINED DESIGN PRESSURES, SEE FBC
 R 301.2(2).
  
 NOTE THAT THE LARGER OPENINGS HAVE HIGHER DESIGN
 PRESSURES, WHICH IS NOT CORRECT. PLEASE FEEL FREE TO
 CONTACT ME IF YOU WISH TO DISCUSS METHODS OF
 DETERMINING DESIGN PRESSURE REQUIREMENTS.
  