2012-04-24 10:51:13 | 2010 FBC | | | | DENIED BY PLUMBING | | | | 1) SUBMIT TWO COPIES OF THE PUMP CURVE FOR THE PENTAIR | | VS-3050 POOL PUMP AND TOTAL DYNAMIC HEAD CALCULATIONS | | SHOWING HOW THE MAXIMUM FLOW RATE OF 120 GPM WAS | | DETERMINED. THE PUMP CURVES THAT I WAS ABLE TO VIEW ON | | LINE HAD CUSTOMIZABLE MAXIMUM FLOW RATES OF OVER 140 | | GPM AND THE FACTORY SET MAXIMUM FLOW RATES WERE CLOSE | | TO 130 GPM. THE MAXIMUM VELOCITY OF 8 FT PER SECOND | | ALLOWED BY ANSI/SPA 4.4 IS EXCEEDED AT THESE MAXIMUM | | FLOW RATES IN 2 & 1/2 " PIPE. FBC 4101.6.3 | | | | 2) THE VALUE FOR POOL SPECIFIED ON THE APPLICATION | | APPEARS TO BE LOW. BASED ON MARSHALL AND SWIFT THE | | VALUE FOR THIS POOL SHOULD BE BETWEEN $14,000 AND | | $15,000. FOR PERMITTING COST THE TOTAL VALUE OF THE | | WORK IS REQUIRED, INCLUDING LABOR, MATERIALS, DESIGN | | FEES, OVERHEAD AND PROFIT (REPLACEMENT VALUE). PLEASE | | ADJUST THE VALUE ACCORDINGLY. CITY AMENDMENTS 108.3 | | | | 3) PLEASE RESPOND TO THE REVIEW COMMENTS IN WRITING. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|