2012-04-24 10:51:132010 FBC
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO COPIES OF THE PUMP CURVE FOR THE PENTAIR
 VS-3050 POOL PUMP AND TOTAL DYNAMIC HEAD CALCULATIONS
 SHOWING HOW THE MAXIMUM FLOW RATE OF 120 GPM WAS
 DETERMINED. THE PUMP CURVES THAT I WAS ABLE TO VIEW ON
 LINE HAD CUSTOMIZABLE MAXIMUM FLOW RATES OF OVER 140
 GPM AND THE FACTORY SET MAXIMUM FLOW RATES WERE CLOSE
 TO 130 GPM. THE MAXIMUM VELOCITY OF 8 FT PER SECOND
 ALLOWED BY ANSI/SPA 4.4 IS EXCEEDED AT THESE MAXIMUM
 FLOW RATES IN 2 & 1/2 " PIPE. FBC 4101.6.3
  
 2) THE VALUE FOR POOL SPECIFIED ON THE APPLICATION
 APPEARS TO BE LOW. BASED ON MARSHALL AND SWIFT THE
 VALUE FOR THIS POOL SHOULD BE BETWEEN $14,000 AND
 $15,000. FOR PERMITTING COST THE TOTAL VALUE OF THE
 WORK IS REQUIRED, INCLUDING LABOR, MATERIALS, DESIGN
 FEES, OVERHEAD AND PROFIT (REPLACEMENT VALUE). PLEASE
 ADJUST THE VALUE ACCORDINGLY. CITY AMENDMENTS 108.3
  
 3) PLEASE RESPOND TO THE REVIEW COMMENTS IN WRITING.
  