Plan Review Notes For Permit 12040244 |
Permit Number |
12040244 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-06-07 16:10:15 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR: | | A) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL | | FL4065-R5 SUBMITTED IS FOR 2007 CODE VERSION. NEED ONE | | FOR CURRENT 2010 CODE VERSION. | | B) ENTRY DOOR AND STORAGE DOOR. DESIGN PRESSURES SHOWN | | ON NOA 07-0618.06 SUBMITTED DON'T MEET THE DESIGN | | PRESSURES CALCULATED BY THE ARCHITECT ON SHEET A-1. | | NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS OR EXCEEDS | | DESIGN PRESSURES CALCULATED BY THE ARCHITECT. | | | | 2- ARCHITECT TO REVIEW & APPROVE IN WRITING (NOT | | SIGNING & SEALING ) ABOVE PRODUCT APPROVALS. SEC. | | 107.3.4.1 CITY AMENDMENTS TO FBC. | | | | 3- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE STORM | | SHUTTERS INSTALLATION. CLEARLY SPECIFY SHUTTERS | | MOUNTING CONDITION (FOR EXAMPLE WALL MOUNTED, ETC) AND | | FASTENER TYPE AND SPACING AS REQUIRED BY PRODUCT | | APPROVAL SUBMITTED TO VERIFY COMPLIANCE WITH THE DESIGN | | PRESSURES OF SEC. R301.2.1.4.3. |
|