Plan Review Notes
Plan Review Notes For Permit 12040244
Permit Number 12040244
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-19 14:40:03RESIDENTIAL (R3) RENOVATIONS BUILDING REVIEW COMMENTS.
 2010 EXISTING BUILDING CODE AND 2010 FLORIDA
 RESIDENTIAL CODE.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, ETC.
 B) REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. THIS
 IS EXISTING HOUSE.
 C) REVISE ITEM #9(A). NOTES ON DRAWING A-1 SAYS "NEW
 R19 INSULATION ON EXTERIOR WALLS". REVISE AS REQUIRED.
 D) HOT WATER SYSTEM IS GAS NOT ELECTRIC. REVISE ITEM
 #14.
 E) A/C EQUIPMENT SIZING CALCULATIONS WERE DONE USING
 WORST CASE SCENARIO. THIS IS NOT ALLOWED. REVISE ITEMS
 #12 AND # 13 ONCE A/C EQUIPMENT SIZING CALCULATIONS ARE
 REVISED.
 F) REVISE TYPE OF DOOR SHOWN ON SHEET 3 OF 5. THERE ARE
 NOT WOOD DOORS. SEE SHEET A-1.
 G) THERE IS NOT GARAGE ON THIS BUILDING. REVISE SHEET 3
 OF 4.
 H) MECHANICAL VENTILATION ON SHEET 4 OF 5. IT SAYS
 THERE IS NOT MECHANICAL VENTILATION. SEE A/C PLAN AND
 REVISE AS REQUIRED. THERE IS MECHANICAL VENTILATION FOR
 BATHROOM.
  
 2- ARCHITECT TO SPECIFY CARBON MONOXIDE ALARMS AS
 REQUIRED BY SEC. R315.
  
 3- ARCHITECT TO SPECIFY THE DESIGN PRESSURES FOR THE
 EXTERIOR DOORS AND WINDOWS. NOTE: ARCHITECT TO TAKE
 INTO CONSIDERATION THAT ACCORDING TO SEC. R301.2.1.4.3
 THIS BUILDING IS LOCATED ON EXPOSURE "C".
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES. NOA 11-0411.02 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT MIAMI-DADE WEBSITE AND
 DOWNLOAD CURRENT NOA.
 B) IN-SWING ENTRY DOOR AS SHOWN ON SHEET A-1.
 C) DOUBLE FRENCH DOORS AS SHOWN ON SHEET A-1.
 D) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL4065-R5 SUBMITTED IS FOR 2007 CODE VERSION. NEED ONE
 FOR CURRENT 2010 CODE VERSION.
 E) STORM PANELS. FLORIDA PRODUCT APPROVAL SUBMITTED IS
 FOR 2007 CODE VERSION. NEED ONE FOR CURRENT 2010 CODE
 VERSION. AND PROVIDE COMPLETE PRODUCT APPROVAL
 INCLUDING ALL THE SHUTTERS DRAWINGS.
  
 5- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 6- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE STORM
 SHUTTERS INSTALLATION. CLEARLY SPECIFY SHUTTERS
 MOUNTING CONDITION (FOR EXAMPLE WALL MOUNTED, ETC) AND
 FASTENER TYPE AND SPACING AS REQUIRED BY PRODUCT
 APPROVAL SUBMITTED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3.
  
 7- CLARIFY IF WINDOWS ARE GOING TO BE REPLACED OR NOT.
 PLANS ONLY SPECIFY DOORS TO BE REPLACED, BUT WINDOW
 PRODUCT APPROVAL WAS SUBMITTED FOR REVIEW.
  
 8- WINDOW ON BEDROOM #3 IS REQUIRED TO HAVE SAFETY
 GLASS. SEC. R308.4(2).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712